1-866-494-4610

Warrick-Gems 26MB1A0F Low Water Cutoff Control 120 VAC 10K Ohm

Warrick-Gems 26MB1A0F Low Water Cutoff Control 120 VAC 10K Ohm
Images for general purposes only. Actual may be different than depicted.
Warrick-Gems 26MB1A0F Low Water Cutoff Control 120 VAC 10K Ohm Warrick (Gems Sensors) 26MB1A0F Low Water Cutoff Control 120 VAC 10K Ohm

Warrick-Gems 26MB1A0F Low Water Cutoff Control 120 VAC 10K Ohm

SKU: 26MB1A0F
UNSPSC: 39121801
Rating: (1)
Quantity Price Stock
4
Usually Ships 2 - 4 Weeks
$603.05     /ea
4
0
$0.00
0
$0.00
0
26MB1A0F
The Warrick (Gems Sensors) 26MB1A0F is a low water cutoff control that operates at 120 VAC with a 10K Ohm direct-acting operation.  UL Recognized and CSD1 compliant, ensuring reliable performance and safety in critical applications.

Features
 
  • Powered Contacts
  • Solid State Reliability
  • Manual Reset Function
  • Modular Plug-In Design
  • Low Voltage Sensor Operation
  • Normally Closed Pushbuttons
  • Power Outage Protection
  • LED Monitoring Indicator
  • Adjustable Time Delays

The 26M Series monitors liquid levels to prevent damage in boilers, tanks, and process systems, caused by low water conditions.  It utilizes an 11-pin octal socket style for easy installation and supports a screw connector socket for secure wiring.
Mode of Operation Direct
Contact Rating 10 Amp Resistive, 1/3 HP
Contact Design 1 Normally Open / 1 Normally Closed
Voltage 120 VAC
Sensitivity 10K Ohm
Temperature Range -40 to 150°F (-40 to 65°C)
Terminal Style Screw Connector
Socket Style 11-Pin Octal
Product Series 26M
Approval U.L. 353 File # MP1430